Update information
BCS Nexto modular - CPU Firmware version 1.14.36.12 (10/06/2025)
The package contains binary files for BCS-NX3003.
Attached revision history and links for the update procedure and transition version.
• Fixed an issue introduced on version 1.12.23.0 where the controller could suffer a retentivity loss (retain data initialized) when powered off within a time window of 5 seconds after the application goes to RUN.
• Info: This version was built with CODESYS Control Runtime Toolkit 3.5.18.60.
IMPORTANT - This update requires the controller running on firmware version 1.9.29.0 or greater, due to new firmware update file format. Link to transition version: